SY50K100F-NB Technical Specifications
Symmetra PX 50kW Scalable to 100kW
Output
Max Configurable Power (Watts)
100.0kWatts / 100.0kVA
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
57 – 63 Hz for 60 Hz nominal
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
Topology
Double Conversion Online
Waveform type
Sine wave
Output Voltage THD
< 2% for 0 to 100% linear load and < 6% for full non linear load
Output Voltage Tolerance
+/-1% static and +/- 5% at 100% load step
Transfer Time
2ms typical
Bypass
Built-in Static Bypass
Input
Input frequency
40 – 70 Hz
Input voltage range for main operations
177 – 239 (208V)V
Input Total Harmonic Distortion
Less than 5% for full load
Input Power Factor at Full Load
0.99
Batteries & Runtime
Battery type
No internal battery – uses external battery system
Efficiency
View Efficiency Graph
Communications & Management
Interface Port(s)
DB-9 RS-232, SmartSlot
Control panel
Multi-function LCD status and control console
Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
Available SmartSlot™ Interface Quantity
2
Physical
Maximum Height
79.17inches (2011MM, 201.1CM)
Maximum Width
23.62inches (600MM, 60.0CM)
Maximum Depth
42.13inches (1070MM, 107.0CM)
Net Weight
966.51lbs. (438.4KG)
Shipping weight
1099.01lbs. (498.5KG)
Shipping Height
84.25inches (2140MM, 214.0CM)
Shipping Width
33.39inches (848MM, 84.8CM)
Shipping Depth
47.64inches (1210MM, 121.0CM)
Color
Black
Environmental
Operating Temperature
32 – 104 °F (0 – 40 °C)
Operating Relative Humidity
0 – 95 %
Operating Elevation
0-3333ft (0-999.9meters)
Storage Temperature
-15 – 40 °C
Storage Relative Humidity
0 – 95 %
Storage Elevation
0-50000ft (0-15000meters)
Audible noise at 1 meter from surface of unit
67.0dBA
Protection Class
NEMA 1
Conformance
Approvals
CSA C22.2 No.107.3-05, FCC Part 15 Class A, ISO 14001, ISO 9001, UL 1778
Standard warranty
1 year on-site repair or replace with factory authorized Start-Up